● Standard
The product is manufactured according to the standard of GB/T 12706 or IEC, BS, DIN and ASTM upon request.
| Type | Name | Application | 
| YJV22 | Copper conductor XLPE insulated steel tape armoured PVC sheathed power cable | For laying in doors、in tunnels and direct in ground,required  | 
| YJLV22 | Aluminium conductor XLPE insulated steel tape armoured PVC sheathed power cable | |
| YJV23 | Copper conductor XLPE insulated steel tape armoured PE sheathed power cable | |
| YJLV23 | Aluminium conductor XLPE insulated steel tape armoured PE sheathed power cable | |
| YJV32 | Copper conductor XLPE insulated fine stecl wire armoured PVC sheathed power cable | For laying in doors、 in tunnels and direct  in ground and wells,  required to bear external mechanical  | 
| YJLV32 | Aluminium conductor XLPE insulated fine steel wire armoured PVC sheathed power cable | |
| YJV33 | Copper conductor XLPE insulated fine steel wire armoured PE sheathed power cable | |
| YJLV33 | Aluminium conductor XLPE insulated fine steel wire armoured PE sheathed power cable | 
Product description
Voltage designation
● The rated voltage of the cable for a given application shall be suitable for the operating conditions in the system in which the cable is used,and is expressed in the form of Uo/U(Um) kV Where:
Uo —The rated power-frequency voltage between conductor and screen or metallic-sheath, for which the cable designed;
U —The rated power-frequency voltage between conductors, for which the cable designed;
Um —The maximum value of the "highest system voltage" for which the equipment may be operated
● Rated voltage of cable applied in three phrase system are given in table.
| 
 U | 
 Um | Uo | |
| First class | Second class | ||
| 1 | 1.2 | 0.6 | 0.6 | 
| 3 | 3.6 | 1.8 | 3.6 | 
| 6 | 7.2 | 3.6 | 6 | 
| 10 | 12 | 6 | 8.7 | 
| 15 | 17.5 | 8.7 | 12 | 
| 20 | 24 | 12 | 18 | 
| 35 | 42 | 21 | 26 | 
The first class cable suitable for one single-phase earth-fault time does not exceed 1 min each time and Max. time mot exceed 8 hours,and not exceed 125 hours in all in one year.
The second class cable suitable for more earth-fault time and more better insulation performance.
Single-core cable is installed in parallel. Adjacent space is equivalent to the diameter of the cable.
Rating factors of current carrying for different soil temperature
| Soil Temperature ℃ | 15 | 20 | 25 | 30 | 35 | 40 | 45 | 
| Rating Factor | 1.07 | 1.04 | 1.0 | 0.96 | 0.92 | 0.87 | 0.83 | 
Rating factors of current carrying for different thermal resistivity
| Rating factors for soil  | 1.0 | 1.2 | 1.5 | 2.0 | 2.5 | 3.0 | 3.5 | 
| Three Cores | 1.0 | 0.943 | 0.877 | 0.792 | 0.736 | 0.675 | 0.641 | 
| Single Core | 1.0 | 0.934 | 0.850 | 0.748 | 0.692 | 0.635 | 0.598 | 
Rating factors of current carrying for different air temperature
| Air Temperature ℃ | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 
| Rating Factor | 1.18 | 1.14 | 1.10 | 1.05 | 1.0 | 0.95 | 0.89 | 
Product display
xlpe,pvc Power cable certificate display
XLPE insulated power cable for rated voltage 3.6/6kV
| Nominal  | Insulation thickness  | YJV、YJY、YJLV、YJLY | YJV62、YJV22、YJLV62、YJLV22 | YJV72、YJV32、YJLV72、YJLV32 | ||||||
| Approx  | Calculated  | Approx  | Calculated  | Approx  | Calculated  | |||||
| YJV  | YJLV  | YJV62  | YJLV62 YJLV22 | YJV72  | YJLV72 YJLV32 | |||||
| 1×25 | 2.5 | 17.7 | 509 | 360 | 21.1 | 739 | 590 | 24.9 | 880 | 730 | 
| 1×35 | 2.5 | 19.0 | 628 | 414 | 22.2 | 863 | 647 | 26.0 | 1009 | 788 | 
| 1×50 | 2.5 | 20.2 | 769 | 478 | 23.6 | 1029 | 736 | 27.4 | 1182 | 889 | 
| 1×70 | 2.5 | 22.0 | 1008 | 586 | 25.2 | 1278 | 856 | 29.0 | 1439 | 1018 | 
| 1×95 | 2.5 | 23.7 | 1274 | 698 | 27.1 | 1576 | 1000 | 30.9 | 1748 | 1172 | 
| 1×120 | 2.5 | 25.1 | 1530 | 805 | 28.3 | 1835 | 1110 | 32.1 | 2018 | 1293 | 
| 1×150 | 2.5 | 26.7 | 1818 | 918 | 30.1 | 2156 | 1256 | 33.9 | 2349 | 1449 | 
| 1×185 | 2.5 | 28.5 | 2179 | 1076 | 31.7 | 2524 | 1424 | 36.5 | 2824 | 1732 | 
| 1×240 | 2.6 | 31.1 | 2762 | 1290 | 34.5 | 3156 | 1683 | 39.1 | 3463 | 1990 | 
| 1×300 | 2.8 | 34.0 | 3399 | 1551 | 38.8 | 4184 | 2336 | 42.0 | 4156 | 2308 | 
| 1×400 | 3.0 | 37.3 | 4273 | 1919 | 41.9 | 5109 | 2760 | 45.3 | 5103 | 2750 | 
| 1×500 | 3.2 | 42.2 | 5430 | 2401 | 47.0 | 6396 | 3374 | 51.4 | 6539 | 3512 | 
| 1×630 | 3.2 | 46.1 | 6843 | 2910 | 51.1 | 7920 | 3991 | 55.5 | 8075 | 4144 | 
| 1×800 | 3.2 | 50.2 | 8560 | 3514 | 55.2 | 9729 | 4683 | 59.6 | 9884 | 4837 | 
| 1×1000 | 3.2 | 53.1 | 10331 | 4136 | 58.7 | 11666 | 5472 | 62.3 | 11759 | 5609 | 
| 3×25 | 2.5 | 35.6 | 1686 | 1234 | 40.2 | 2489 | 2037 | 43.6 | 3383 | 2932 | 
| 3×35 | 2.5 | 38.2 | 2089 | 1443 | 43.0 | 2968 | 2313 | 47.4 | 4333 | 3644 | 
| 3×50 | 2.5 | 41.0 | 2530 | 1651 | 45.8 | 3470 | 2585 | 50.2 | 4917 | 3996 | 
| 3×70 | 2.5 | 44.7 | 3355 | 2083 | 49.7 | 4399 | 3128 | 54.1 | 5953 | 4682 | 
| 3×95 | 2.5 | 48.5 | 4178 | 2440 | 53.5 | 5309 | 3572 | 57.9 | 7010 | 5272 | 
| 3×120 | 2.5 | 51.3 | 4937 | 2751 | 56.7 | 6183 | 3997 | 61.1 | 7965 | 5779 | 
| 3×150 | 2.5 | 55.0 | 5965 | 3251 | 60.6 | 7326 | 4612 | 65.0 | 9214 | 6500 | 
| 3×185 | 2.5 | 58.6 | 7028 | 3704 | 64.2 | 8475 | 5161 | 68.6 | 10473 | 7193 | 
| 3×240 | 2.6 | 64.7 | 8928 | 4489 | 70.5 | 10561 | 6118 | 74.9 | 12789 | 8309 | 
| 3×300 | 2.8 | 70.9 | 11004 | 5432 | 76.9 | 12813 | 7242 | 85.0 | 16326 | 10755 | 
| 3×400 | 3.0 | 77.8 | 13659 | 6563 | 85.4 | 16492 | 9411 | 92.3 | 19528 | 12500 | 
| 3×500 | 3.2 | 88.3 | 17519 | 8389 | 96.1 | 20771 | 11664 | 103.0 | 24204 | 15146 | 
| 3×630 | 3.2 | 96.7 | 21941 | 10083 | 105.1 | 25639 | 13797 | 112.0 | 29392 | 17603 |