Type: MCP (Multicore) rated voltage: 0.66/1.14kV | ||||||||||
Cores * cross section | Nominal thickness of power cores insulation | Nominal thickness of sheath | Overall diameter for reference | Approx, weight | D.C. Resistance of conductor at 20°C | |||||
3*25+1*6+3*2.5 | 2.0 | 6.0 | 41.1 | 2458 | 0.795 | |||||
3*35+1*6+3*2.5 | 2.0 | 6.0 | 44.0 | 2965 | 0.565 | |||||
3*50+1*10+3*2.5 | 2.2 | 7.0 | 51.6 | 3906 | 0.393 | |||||
3*70+1*16+3*6 | 2.2 | 7.0 | 56.0 | 5134 | 0.277 | |||||
3*95+1*25+3*4 | 2.4 | 7.0 | 62.1 | 6067 | 0.210 | |||||
3*120+1*25+3*4 | 2.6 | 7.0 | 66.5 | 7292 | 0.164 | |||||
3*150+1*35+3*4 | 2.6 | 7.0 | 71.6 | 8625 | 0.132 | |||||
Remarks: The core of the ground line and the core of the control line in the table are the minimum cross sections. If the section exceeds the section, it can be assigned according to the schedule.(Weight and external diameter can be consulted by our company) |
Annexe Table | ||||||||||||||
cross sections of power cores mm2 | min. cross sections of ground cores mm2 | matched size of control cores | ||||||||||||
25 | 6 | 3*2.5 | 4*2.5 | 7*2.5 | 3*4 | 4*4 | 7*4 | |||||||
35 | 6 | 3*2.5 | 4*2.5 | 7*2.5 | 3*4 | 4*4 | 7*4 | |||||||
50 | 10 | 3*2.5 | 4*2.5 | 7*2.5 | 3*4 | 4*4 | 7*4 | |||||||
70 | 16 | 3*2.5 | 4*2.5 | 7*2.5 | 3*4 | 4*4 | 7*4 | |||||||
95 | 25 | 3*2.5 | 4*2.5 | 7*2.5 | 3*4 | 4*4 | 7*4 | |||||||
120 | 25 | 3*2.5 | 4*2.5 | 7*2.5 | 3*4 | 4*4 | 7*4 | |||||||
150 | 35 | 3*2.5 | 4*2.5 | 7*2.5 | 3*4 | 4*4 | 7*4 |