Der Schwerpunkt liegt auf der Forschung, Entwicklung, Produktion und dem Vertrieb von Drähten und Kabeln.

Marinekabel (旧)

about marine cable
Marine cable--specialty cable
Marine cable is a cable product designed for ships and ocean engineering, which is a special cable. Its product models are diverse, such as IEC60092-353, IEC60092-353, IEC60092-376. technical specifications, with high resistance to pressure, abrasion, corrosion and other characteristics. They are usually applied to power, lighting, communication and control systems in ships. In terms of usage scenarios, it can be widely used in all kinds of ships, such as cargo ships, passenger ships, fishing boats, etc.. Especially important is that it has excellent fireproof performance, which can effectively protect the safety of ships during navigation. These marine cables provide reliable support for the stable operation of ships. If you are looking for a marine cable supplier, Jiangnan Cable is your best choice as a top power cable/specialty cable manufacturer in China.
keine Daten

Short circuit current ratings

1. The following short current ratings are for cables normally operating at a maximum

conductor temperature of 90℃

2. As a basis of the calculation,the theoretical temperature that arises in the conductor

during a short circuit is 250℃ in accordance with IEC60724.

3. EPR insulation are capable of withstanding of short term temperature up to 250℃

4. The short circuit current rating for copper conductors given in the table are values for 1

sec.and for other duration the current may be calculated by the following formular;

lt: Short circuit current fort second (A)

l1: Short circuit current for 1 second (A)

t: Short circuit duration(second )

5. The duration of short circuit based on these assumptions should be between 0.2 sec

and 5 sec

Conductor area

Short circuit current for 1sec

Conductor area

Short circuit current for 1sec

mm2

A

mm2

A

1.5
2.5
4
6
10
16
25
35
50

143
215
358
572
859
1431
2289
3577
5008
7154

70
95
120
150
185
240
300

10016
13593
17170
21463
26470
34340
42925

keine Daten
Spezialisiert auf Produktion, Vertrieb und R&D von Drähten und Kabeln

Wuxi Jiangnan Cable Co., Ltd. wurde im April 2012 in Hongkong gelistet. ist ein nationales Schlüsselunternehmen für Hoch- und Neutechnologie, das auf die Produktion, den Vertrieb und die Forschung im Bereich Kabel spezialisiert ist & Drähte. Das Unternehmen erstreckt sich über eine Fläche von mehr als 650.000 Quadratmetern und verfügt über ein Gesamtvermögen von mehr als 8 Milliarden Yuan. Mit mehr als 1.500 Sätzen moderner Produktions- und Prüfgeräte im In- und Ausland haben wir zahlreiche Managementsystem-Zertifizierungen bestanden 

Warenpräsentation
keine Daten

Conductor resistance

Resistance communication formula

R=P*L/A

R: Resistance in ohm per phase

p: Specific resistance,Ω.mm²/m

A: Conductor area,mm²

L: Conductor length,m

Resistance as a Function of Temperature

R=RO[1+a(t-20)]

RO: Resistance at t=20℃

t: Conductor temperature,℃

α: 0.00393 for copper

Conductor D.C.Resistance of Tinned Annealed Stranded Copper at 20℃

Conductor area

Max.resistance at 20℃

Conguctor area

Max.resistance at 20℃

Class2

Class5

Class2

Class5

mm²

ohm/km

mm²

ohm/km

0.5

36.7

40.1

70

0.270

0.277

0.75

24.8

26.7

95

0.195

0.210

 

18.2

20.0

120

0.154

0.164

1.5

12.2

13.7

150

0.126

0.132

2.5

7.56

8.21

185

0.100

0.108

4

4.70

5.09

240

0.0762

0.0817

6

3.11

3.39

300

0.0607

0.0654

10

1.84

1.95

 

 

 

16

1.16

1.24

 

 

 

25

0.734

0.795

 

 

 

35

0.529

0.565

 

 

 

50

0.39

0.393

 

 

 

Current reting for continous service

Current ratings for EPR and XLPE insulated power cable

Current rating of EPR and XLPE insulated power cable in continuous service at maximum rated temperature of 90℃ in accordance with IEC 60092-352(2005)Annex B.4.with ambient temp.45℃

Conductor area

1core

2core

384c0f6

mm2

Amp

Amp

Amp

1

19

16

14

1.5

23

20

16

2.5

40

26

21

4

51

34

28

6

52

44

36

10

72

61

50

16

96

82

67

25

127

108

89

35

157

133

110

50

196

167

137

Leiterbereich

1Kern

2Kern

384c0f6

mm2

Ampere

Ampere

Ampere

70

242

206

169

95

293

249

205

120

339

288

237

50

389

331

272

185

444

377

311

240

522

444

365

300

601

511

421

 

Gleichstrom

Wechselstrom

Gleichstrom

Wechselstrom

Gleichstrom

Wechselstrom

400

690

670

587

570

483

469

500

780

720

663

612

546

504

630

890

780

757

663

623

546

* The tabled current ratings must be adjusted for ambient air temperatures other than45℃ by multpying the rating factors in the following table

Ambient temp.℃

35

40

 45

50

55

60

65

70

75

80

Rating factors

1.10

1.05

1.00

0.94

0.88

0.82

0.74

0.67

0.58

0.47

For cabies with more than 4 cores,the current ratings are given by the following formular:

NO.

1.0mm²Amp

1.5mm²Amp

2.5mm²Amp

NO.

1.0mm²Amp

1.5mm²Amp

2.5mm²Amp

I1=Current rating for single cores

5

12

14

19

16

7

9

13

7

9

13

17

19

7

9

12

N=Number of cores

10

 

12

15

24

6

8

11

12

 

11

14

27

6

8

11

 

 

11

13

33

6

7

9

Installation Recommendation

1.  Minimum Bending Radius: The minimum recommended installation bending radinus shall be in accordance with IEC60092-352 as following:

Bending radii for cables rated up to 1.8/3kV

Cable construction

Overall dia.of cable(D)

Min.radius of bend

Insulation

Covering

Thermoplastic or thermosetting with cicular copper conductors

Unarmored or unbraided

≤25mm

4Da

>25mm

6D

Metal braid screened or armored

Any

6D

    Metal wire armored,metal tape armored or metal-shaped

Any

6D

Composite polyester/metal tape screened units or collective tape screen

Any

8D

Thermoplastic or thermosetting with shaped copper conductors

Any

Any

8D

Mineral

Hard metal sheathed

Any

6D

6D for defined circuit integrity

Bending radi for cables rated at 3.6/6 (7.2)kV and above

Cable Construction

Overall diameter of cable (D)

Min.radius of bend

Single-core Cable

Any

12D

Three-core Cable

Any

9D

2. Pulling tension

The cable puling tension during installation can be estimated through the following formula:

For armored cable

(P=50Nxtotal  criss  section  area  of  conductors)

For unarmored cable

(P=25N×total cross section area of conductors)

Additional  tension  will  be  supplied  form  the  braid  and  the  insulation  and  sheathing  material

Our Related Certifications 
keine Daten
Our related products
keine Daten
Wir sind ein nationales Schlüsselunternehmen für Hoch- und Neutechnologie, das auf Produktion, Vertrieb und Forschung im Bereich Drähte und Kabel spezialisiert ist.
Ansprechpartner: Wilco Zhong
Kontaktnummer: 86-13372003527
WhatsApp: 86-13372003527
Ansprechpartner : Kelly Lu
Kontaktnummer: 86-17368475715
WhatsApp: 86-17368475715
Urheberrecht© 2024 Jiangnan-Kabel  | Seitenverzeichnis
Customer service
detect